MIL-PRF-13312R
complete and accurate.
4.3.3.6.2.1 Electrical instruction plate inspection. Visually verify that type II refrigeration units have
an electrical instruction plate containing correct power source information located near the electric
supply junction box.
4.3.3.6.3 Control and gage nameplate inspection. Visually verify that all controls and gages have
nameplates.
4.3.3.6.4 Electrical wiring inspection. Visually verify that all wiring is marked to allow
identification with the wiring diagram on the instruction plates.
4.3.3.7 Interchangeability certification. The contractor shall certify that all component parts of the
refrigeration unit shall be interchangeable with the same parts of other units of the same type furnished
under the same contract.
4.3.4 Operating environment requirements verification. All operating environment requirements
shall be verified as follows.
4.3.4.1 Ambient temperature testing. All refrigeration units shall be tested for operation in high
temperature ambients as specified in 4.3.4.1.1. Type I refrigeration units shall also be tested for
operation in low temperature ambients as specified in 4.3.4.1.2.
4.3.4.1.1 High temperature operation test. The refrigeration unit shall be heat soaked for 6 hours at
an ambient temperature of 1250F minimum. With air entering and surrounding the condenser and the
condenser section maintained at 1250 F minimum, the unit shall be started and operated for 1 hour with
its control set at 400F, then shut off. Air velocity around the condenser section shall not exceed 100
feet per minute. After 2 minutes, the unit shall be restarted and operated for one hour with its control
set at 400F, then shut off. This procedure shall be followed for a total of 4 hours with the unit
continuing to operate.
4.3.4.1.2 Low temperature operation test. The type I units, complete with battery and fuel, shall be
placed in a temperature controlled room maintained at 00 F,+ 20F, for 12 hours. On completion of the
cold soak period, the unit shall be automatically started and operated for a period of 1 hour during
which time the cold room shall be maintained at 00 F + 150F.
4.3.4.2 Rainfall test. The refrigeration unit shall be mounted in a simulated container and fresh
water sprayed on the unit at no less than 3 inches per hour at an average downward angle of 45 degrees
to simulate rainfall on the exposed surfaces of the unit. The front, top, and two sides of the unit shall
be individually sprayed for 30 minutes while not operating. The refrigeration unit shall then be started
and operated for 30 minutes while the spray continues. A visual verification shall be done to insure no
leakage occurred in the evaporator section, electrical control or junction boxes, the food storage area of
16
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business